NEW QUESTION 72
NETCOL5000-A35KW uses an electronic expansion valve.

  • A. TRUE
  • B. FALSE

Answer: B

 

NEW QUESTION 73
Fusionllodule2000 UPS is listed and configured?

  • A. Integrated UPS cabinet
  • B. Integrated power distribution cabinet
  • C. Precision power distribution cabinet

Answer: A

 

NEW QUESTION 74
BCB-BOX is an optional part of UPS5000-E, used for connection control between battery pack and UPS system, with overload, short circuit protection and remote management tripping functions.

  • A. False
  • B. True

Answer: B

 

NEW QUESTION 75
When the Huawei air-cooled air-conditioning compressor is turned on for the first time, the crankcase heating belt needs to be preheated for more than () hours.

  • A. 0
  • B. 1
  • C. 2
  • D. 3

Answer: C

 

NEW QUESTION 76
The form of humidifier adopted by the row-level chilled water intelligent temperature control product NetCol5000-C032H is ( ). (Fill in the blank)

  • A. Wet film

Answer: A

 

NEW QUESTION 77
UPS5000-E can press the battery cold start button on the module to start the inverter without the main bypass input, and the system will automatically enter the battery inverter mode.

  • A. FALSE
  • B. TRUE

Answer: B

 

NEW QUESTION 78
UPS5000-A can significantly reduce the harmonic pollution to the power grid. In the case of a linear full number, the input electrical and hydraulic distortion nmi is ()

  • A. 0.02
  • B. 0.05
  • C. 0.01
  • D. 0.03

Answer: C

 

NEW QUESTION 79
RH2288 server supports () power input.

  • A. 0
  • B. 1
  • C. 2
  • D. 3

Answer: A

 

NEW QUESTION 80
The communication option cards of UPS2000G are only MODBUS and SNMP.

  • A. True
  • B. False

Answer: B

 

NEW QUESTION 81
A system is configured with 5H battery backup time, and the discharge termination voltage of the battery cell should select?

  • A. 1.80V
  • B. 1.75V
  • C. 1.60V
  • D. 1.67V

Answer: B

 

NEW QUESTION 82
The static load of the FusionModule2000 cabinet can support 2400KG.

  • A. False
  • B. True

Answer: B

 

NEW QUESTION 83
On the NETECO interface, a module can only bind () ECC800 devices.

  • A. 0
  • B. 1
  • C. 2
  • D. 3

Answer: A

 

NEW QUESTION 84
Which of the following are the basic functions of NETECO? (Multiple choice)

  • A. Video Management
  • B. Report Management
  • C. User Management
  • D. Access Management

Answer: A,B,C,D

 

NEW QUESTION 85
Using UPS5000-E (50kVA power module), the actual load is 160kW, the rack is 1+1 redundant, the single-machine backup power scheme is adopted, the backup power scheme for each machine, 3 sets of batteries per rack, 40 cells per set, the capacity of the main switch box is:

  • A. 320A
  • B. 630A
  • C. 250A
  • D. 500A

Answer: B

 

NEW QUESTION 86
If the UPS5000-400K cuts the bypass and closes the maintenance side station, both the main power module and the bypass module stop working.

  • A. TRUE
  • B. FALSE

Answer: B

 

NEW QUESTION 87
The closed hot and cold aisle system can improve cooling efficiency and reduce energy consumption.

  • A. False
  • B. True

Answer: B

 

NEW QUESTION 88
In ECO mode, when the input is stable, the UPS works in () state.

  • A. Main circuit inverter
  • B. battery
  • C. Maintenance Bypass
  • D. Bypass

Answer: D

 

NEW QUESTION 89
The rated voltage of the cell (CELL) in the VRLA battery is ().

  • A. 2V
  • B. 6V
  • C. 12V
  • D. 1V

Answer: A

 

NEW QUESTION 90
The main unit of UPS5000-(DKVA power module) occupies a small area, saving the space of the computer room, and the area is only?

  • A. 1 square meter
  • B. 1.5 square meters
  • C. 0.8 square meters
  • D. 0.5 square meters

Answer: D

 

NEW QUESTION 91
When there are multiple computer rooms and they are monitored at the same time, the hierarchical deployment of the monitoring system may occur.

  • A. FALSE
  • B. TRUE

Answer: B

 

NEW QUESTION 92
UPS2000-G- (6-20KVA) battery is not connected, which does not affect the normal power supply of the system.

  • A. False
  • B. True

Answer: B

 

NEW QUESTION 93
......